Exams

The product portfolio of BEZ TRANSFORÁTORY a.s. is systematically tested in accordance with STN EN 60076 in an independent and accredited laboratory designed for product certification. All products meet the latest technical requirements of applications and installations.

Guaranteed quality

The high level of quality is ensured by the unit tests to which each individual transformer in the range is subjected:

  • measurement of winding insulation resistance
  • measurement of no-load voltage transfer and phase rotation check
  • measurement of ohmic resistance of the winding
  • test by applied voltage from a foreign source
  • induced voltage test
  • measurement of losses and no-load current
  • measurement of losses and short-circuit voltage (impedance)
  • measurement of partial discharges (epoxy transformers)

Other control operations carried out in connection with piece tests are:

  • measurement of the breakdown voltage of a liquid dielectric,
  • checking the completeness and integrity of the product,
  • checking the wiring of electrical circuits of accessories.

Piece tests are carried out in accordance with EN 60076-1, EN 60076-3, EN IEC 60076-11. Customer requirements for various other test procedures and conditions require an individual approach and discussion with the development team and the test laboratory. All measuring instruments have metrological continuity and are periodically calibrated. The test result is issued in the form of a test report, which is available to the customer before the transformer is shipped from our factory.

The type test serves to demonstrate that the transformers meet the prescribed requirements, which do not fall into the category of unit tests. A prototype transformer is considered to be representative of other transformers if it is manufactured according to the same drawings using the same technology and materials in the same factory. The type test is performed to verify and demonstrate the high quality of the transformer design and to confirm its technical performance according to the technical standards STN EN 60076-2, STN EN 60076-3, STN EN 60076-10, STN EN IEC 60076-11.

  • warming test,
  • determination of the noise level,
  • atmospheric pulse test,
  • measurement of losses and no-load current at 90% and 110% of rated voltage.

A special test is a test other than a type or piece test agreed between the manufacturer and the customer.
This category includes, for example:

  • special electrical strength test STN EN 60076-3,
  • hot-spot measurement STN EN 60076-2, STN EN IEC 60076-11,
  • measurement of the loss factor (tan δ) and capacitance resistances of the insulation system,
  • measurement of gases dissolved in a liquid dielectric,
  • short-circuit resistance test STN EN 60076-5.